HomeProductContactorVacuum Contactor

Vacuum Contactor 7.2~12kV (VACG3-4)

This series contactor consists of electrical insulating frame,metal base,shaft and crank arm,electromagnetic systems,permanent magnet,power modules,auxiliary switches and vacuum interrupters.While control voltage goes across the electromagnetic coil,the armature drives the crutch rotating to open the main contact in the vacuum interrupter.
DESCRIPTIONMain technical parameter

Model NO.

VACG3-160,250,400,630A/7.2(12)-4

Certification

ISO9001, CE, CCC

Rated Operating Frequency

300 times/h

Mechanical Life

1,000,000 times

Over Travel

Min:1.2mm

Opening Time

Max:120ms

Closing Time

Max:150ms

Trademark

VACEM

Origin

Wenzhou, China


1.General description  

    This series contactor consists of electrical insulating frame, metal base, shaft and crank arm, electromagnetic systems, permanent magnet, power modules, auxiliary switches and vacuum interrupters. While control voltage goes across the electromagnetic coil, the armature drives the crutch rotating to open the main contact in the vacuum interrupter. Meanwhile, auxiliary switch cuts off power of electromagnetic coil, the armature drive the crutch rotating to open the main contact in the vacuum interrupter. Meanwhile, auxiliary switch cuts off power of electromagnetic coil, turns to be permanent-magnet maintenance. After power broke by control circuit, energy storage power of power module discharges to electromagnetic coil for degaussing, and the main contact broke under the function of opening spring.


2.Normal using conditions

a. Environment temperature : -5ºC~+40ºC, and average value is no more than +35ºC within 24 hour.

b. Altitude: no more than 1000m.

c. Atmospheric conditions: monthly highest humidity in the most wet month is no more than 90% and monthly average minimum temperature shall be 25ºC. Condensation on the products due to temperature changes shall be considered.

d. Impact vibration: The place is without extensive shaking, impact, and vibration.

e. The place is without explosion hazard, etchant gas and sleet.

f. No rain and snow in places

g. Pollution degree: Three grade

h. Installation type: .III

i. Installation condition: Slant angle between installation surface andvertical surface is no more than 15°.


Inquiry

If you have any enquiry about quotation or cooperation,please feel free to email us at vacem@vacem.cn
or use the following enquiry form. Our sales representative will contact you soon. Thank you for your interest in our products.

top

Copyright © 2021 Vacem Electrical Co, Ltd.& wenzhou vacem technology Co, Ltd.

Powered by:Otree | Privacy Policy | Sitemaps | XML